Double Regulating Valves

Double Regulating Valve:
Peter Smith Valve Fig.BV307 Bronze (Gunmetal Double Regulating Valve) 15mm-50mm bore flanged, and Fig.BV203 Cast Iron Double Regulating Valve 65mm-200mm bore flanged.

What is a Double Regulating Valve?:
These are Y-Pattern Oblique globe valves supplied with two pressure test points to provide flow measurement, regulation and isolation.

The Double Regulating feature allows the valve to be used for isolation and to be reopened to its pre-set position to maintain required flow rate; and regulation.

Primarily used in a ring main piping circuit requiring double regulating valves for the system balancing and commissioning of heating systems.

How the valve works:
Our Fig.BV307 & BV203 are manually operated by handwheel and the opening of the valve is set at commissioning by a locking device to control the flow through the valve. The valve can be closed by manually operating the handwheel to isolate the flow through the valve.

Typical uses and applications the valve is used in:
Double Regulating Valves may be found in fluid regulating & industrial heating systems.

They can be used in High Temperature Hot Water (HTHW), Medium Temperature Hot Water (MTHW), Low Temperature Hot water (LTHW) and Cold ‘clean’ water applications.

Float Valves

What is a Float Valve?
A Float Valve controls the discharge of a pipeline fluid into a small tank automatically to a top level of fluid required. The float mechanism is fitted to the small bore valve and falls on the water level to open the valve and rises on the water level to close the valve.

Equilibrium Float Valves (For larger bore pipe discharge):
Our Fig. 501 Equilibrium Ball float Valve range which is WRAS approved (Water Regulation Advisory Scheme) for potable water, can be fitted to a larger bore inlet pipe 2” (50mm) to 12” (300mm) bore to automatically control the water flow by use of the float mechanism as above and the inlet line pressure operating a pressure balancing cylinder in the valve enabling the larger bore equilibrium valve to control the water flow into reservoirs and large water storage tanks, for drinking water and sprinkler fire protection system tanks.

Equilibrium Float Valve Construction
Materials used in the construction of the valve will include:
• Body/Cover – Cast Iron to Cover BSEN 1561 EN GJL 250
– Tough black Rilsan nylon coating heat fused to body/cover
• Seat Ring/Cylinder- Gunmetal to Valve Seat BS EN 1982 CC491K
• Disc – EPDM Rubber bonded to steel reinforcing plate
• Piston Seal – EPDM Rubber
• Float – Tough black Rilsan nylon coating heat-fused to steel float